Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T00CM04864
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2001 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
06/08/2001 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) NEUTRAL WIRES NOT PERMITTED TO BE PAIRED UNDER A SINGLE LUG SCREW 2) WEATHERPROOF COVER REQUIRED AT OUTLET NEAR A/C CONDENSOR 3) A/C DISCONNECT REQUIRES FUSES SIZED PER LABEL |