Permit: T00CM04863

Parcel: 114468460

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM04863

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/23/2001 FRAMING Approved IVRS - Inspection 0000*
05/22/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) PEX 12" AWAY FROM FLUE 2) DOOR JAMB HINGE SIDE 3) CUT NAIL PLATES BELOW PLENIUM 4) KITCHEN WALLS NOT SECURE 5) STUD CUT AT KITCHEN VENT/OVEN 6) TAPE JOINT KITCHEN VENT 7) REAR BED WALL SPLICE BOTTOM PLATE NOT IN LINE 8) GAS TEST OK
05/07/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) WATER LINES 6" FROM FURN FLUE? 2) FIX TRUSSES AT FRONT 3) CHECK FURN FLUE HT OVER GARAGE PLATFORM 4) SOFFIT BLK AT GARAGE FURN FLUE 5) HD NUTS 6) SECURE DRYER VENT AT OFFSET 7) DIVERTER STUD NOTCHED TOO DEEP 8) MISSING STUD AT RANGE HOOD 9) CHECK ALL PLATE BOLTS 10) SECURE BROKEN PLATE AT FOOT VENT 11) SECURE KITCHEN PONI ? WALL TO FLR 12) HAVE TRUSS CO CHECK GUSSET PLATES IN KITCHEN AND FAMILY ROOM CEILING NOT CENTERED ON JOINTS 13) 2 X 4 JOISTS REAR GIRDER CUT SHORT NEED BLOCKS OR HANGERS 14) CHECK BOTTOM PLATES FOR CUT NAILS 15) DIVERTER STUD NOTCHED TO DEEP 16) NAIL BACK WALL TO MASTER TOILET 17) STIFF LEG SCUTTLE HOLE TO TRUSS 18) FRONT DOOR HINGE BOTTOM PLATE NOT SECURE 19) GAS TEST OK