Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/24/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/22/2001 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) SERVICE PANEL LABEL ALL CIRCUITS, PLUG KNOCK OUT HOLE 2) MISSING HOSE BIB WATER SERVER 3) NEED GAS COCK AT RANGE 4) CAULK LOG LITER |