Permit: T00CM04854

Parcel: 118037970

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/20/2000 FRAMING Approved IVRS - Inspection 0000*
12/19/2000 FRAMING Partial Approval IVRS - Inspection 0000*/1. ITEMS #4,5 PART OF #6. 2. PROVIDE APPROVED STRAPS FOR ABS VENTS AT HORIZONTAL RUNS PLUMBERS TAPE NOT APPROVED. 3. REMOVE COMBUSTIBLE MATERIAL FROM HOT WATER FLUE VENT. 4. INSTALL TUB/SHOWER.
12/15/2000 FRAMING Denied IVRS - Inspection 0999*/1. BLOCK SHEATHIN UNDR MECHANICAL RUNNING. 2. STRAP BEAM HORIZONTALLY AT MASTER STRUCTUAL WALL. 3. PROVIDE CLEANOUTS AS PER PLAN. 4. SEAL FLOOR PENETRATIONS OVER 1/4 AT KITCHEN DRAIN SEAL FLOOR PVC FOR ELECTRIC ADJACENT TO KIT. DRAIN. 5. STRAP OVER KNOTCH DBL TOP PLATE AT CONDENSATION. 6. MAKE UP ELECTRICAL ROMEX AT FURNACE PROTECT ELEC. ROMEX THRU OUT WITHIN 1/4 FROM EDGE OF STUD.