Permit: T00CM04840

Parcel: 133142210

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/15/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
02/13/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* 1)CONDENSATE DRAIN LINE FROM 2 EVAP. COILS IN WALK-IN COOLER STEP UP TO 1". 2) INSTALL CONDENSATE DRAINS ON A/C UNITS. 3) PERMANENTLY LABEL EQUIPMENT ON ROOF ( A/C=1, EF-1, EVAP COOLER-1, ETC...).
4) ANCHOR ELECTRICAL DISCONNECTS ON ROOF.
5) PROVIDE ELECTRICAL SERVICE RECEPTICALS WITH-IN 25' OF EQUIPMENT