Permit: T00CM04840

Parcel: 133142210

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/21/2000 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
WASTE AND VENT SYSTEM OK
ALL CORRECTIONS HAVE BEEN MADE
OK TO BACKFILL TRENCH
11/15/2000 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*
3" FLOOR SINK SANTEE ON ITS BACK CHANGE TO 3"X2" COMBO AND ROLL AT A 45 DEGREE FOR VERTICAL VENT
3" GUAGE TRAP REDUCTED TO 2" CONSIDERED AN OBSTRUCTION
VENT FOR GUAGE TRAP BELOW WEIR NOT APPROVED
ROUGH/ SOIL FOR BATHROOMS OK WATER TEST OK
RISERS ONLY OK TO COVER
HAND SINK AND 3 FLOOR SINKS OK WATER TEST OK RISERS ONLY TRANSITION FITTINGS OK OK TO COVER