Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/02/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. WATER HEATER AND FURNACE VENTS WITHIN 4 FEET OF VERTICAL WALL MUST EXTEND 1 FT ABOVE WALL. 2. FURNACE VENT MISSING WEATHER CAP 3. A.B.S. PLASTIC VENTS ON ROOF MUST HAVE LATEX PAINT PROTECTION. 4. MAX ALLOWED A/C FUSE /CB-45 AMP. 50 INSTALLED. |