Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/26/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 12/04/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) IDENTIFY GROUNDING CONDUCTOR AT TERMANAL. 2.) USE FUSES AS PER PLAN 3.) INSTALL ACORN GROUND CLAMP AS PER MANUFACTURE. 4.) LABEL PANEL "L-1" ON OUTSIDE OF COVER. 5.) PROVIDE LETTER VERIFYING TORQUE VALVES 6.) VERIFY WATER BOND AS PER PLANS. |
| 11/14/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
|