Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/08/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 10:30 AM WENT TO MUSIC HALL WALKED AROUND COULD NOT LOCATE ANYONE FROM CRICKET COMM |
|
| 02/06/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* WORKING CLEARANCE I FRONT OF ROOF LEVEL PANELBOARD VIOLATED. CONDUITS PROTRUDE OUT FROM BOTTOM PERMANENTY ADDRESS METER BASE NEED MAIN BONDING JUMPER AT MAIN DISCONNECT NEED TO PUT GROUND WIRE INTO WEDGE OF ACCESS CLAMP AT ROD |