Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/19/2001 |
MECHANICAL - FINAL |
|
Approved |
OK FOR C OF O. |
| 11/14/2001 |
MECHANICAL - FINAL |
|
Denied |
PROVIDE COVERS OVER FLUE VENT OUTLETS ON AC UNITS ON ROOF. CANNOT REDUCE SIZE OF CONDENSATE PIPE ON TRAP AT AC-1 ON ROOF. MUST BE SAME SIZE AS THE OUTLET. INUSLATE T-WYE ABOVE CEILING AT FRONT OF STORE PROVIDE OUTSIDE AIR HOODS ON AC UNITS AS PER PLANS. INSTALL DRAIN PIPE ON EVAP. COOLERS. |
| 09/06/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
OK FOR TEMP C OF O |