Permit: T00CM04774

Parcel: 136238630

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
09/13/2001 MECHANICAL - HOODS Approved IVRS - Inspection 0000*
09/12/2001 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*O.K. FOR 2ND LAYER OF WRAP BE SURE 1ST LAYER GOES ALL THE WAY TO TOP OF DUCT.
09/11/2001 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection 0000*
09/07/2001 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection 0000*EXHAUST DUCT WRAP IS NOT WHAT IS ON APPROVED PLANS.
09/05/2001 MECHANICAL - HOODS Denied IVRS - Inspection 0999*CLEANOUT ACCESS DOORS ON GREASE DUCT MUST BE PER 3M SPECS. OK FOR 1ST LAYER OF WRAP.