Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2001 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 06/04/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1)PROPER CLEARANCE IN FRONT OF FURNANCE BLOCKED BY DOOR.2)CH. PROPER SIZE FOR COMB.AIR DUCT.3)COLD AIR RETURN PLENUIM.PLENUIMS CANNOT HAVE EXPOSED COMBUSTIBLE. | |