Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 02/05/2002 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 09/05/2001 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PROVIDE PROOF OF FOOTINGS ON NORTH AND SOUTH WALLS, EXPOSE FOOTING ONE LOCATION EACH WALL TO A DEPTH OF 12" BELOW GRADE 2) HOUSE SUB PANEL MUST HAVE A MAIN SERVICE DISCONNECT 3) MAIN HOUSE SUB PANEL MUST HAVE AN APPROVED GROUND SYSTEM, INSTALL TWO EACH 8 FOOT GROUND RODS AT LEAST 6' APART CONNECTED TO MAIN SUB PANEL WITH A CONTINOUS #4 GROUND WIRE 4) MAIN HOUSE SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR WITH ALL WHITE WIRES ON NEUTRAL BAR AND ALL GROUND WIRES ON GROUND BAR 5) POST FOOTING-OK |