Permit: T00CM04706

Parcel: 11105100A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/16/2000 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
11/15/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
GROUNDED TYPE SWITCHES REQUIRED IN PLASTIC BOXES 380-9
CONDUCTORS IN 2 1/2" CONDUIT TO BE DE-RATED TO 80% 310-15B N.E.C.
OK TO COVER WALLS EXCEPT BEHIND SERVICE, NORTHEAST WALL.
A REINSPECTION FEE WILL BE ASSESTED NEXT INSPECTION IF NOT IN COMPLAINCE WITH PREVIOUS WRITE- UP AND N.E.C.
11/09/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
11/09/00 SIZE NEUTRAL ACCORDINLY TO LOADS
DERATE CURRENT CARRING CONDUCTORS IN 2" CONDUIT
STRAP A/C CABLE AS PER CODE
MAKE UP NOT FINISHED BOX BY DOOR SOUTHSIDE
11/07/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*
NEUTRALS AND GROUNDS MUST BE SEPERATED
AT 12X2 J-BOX, N OT ALLOWED ON SAME GROUND BAR 250-24-1
PUSH-IN PLASTIC BUSHING NOT ALLOWED OR APPROVED IN PANCAKE BOXES FOR EXTERIOR LIGHTING 373-5 B
WIRING METHODS IN PATIENT CARE AREAS (LIGHT SWITCHES) MUST COMPLY WITH 517-13 N.E.C.
DE RATE CURRENT CARING CONDUTORS INSTALLED IN 2" CONDUIT. 310-15B N.E.C.
INSTALL PERMANENT ADDRESS LABEL ON SERVICE
11/06/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
BOND JUNCTION BOX 250-96
LOOSE FITTINGS
NEED ACCESS TO ALL AREAS
STRAP ALL CONDUITS AS PER CODE