Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2000 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 11/15/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* GROUNDED TYPE SWITCHES REQUIRED IN PLASTIC BOXES 380-9 CONDUCTORS IN 2 1/2" CONDUIT TO BE DE-RATED TO 80% 310-15B N.E.C. OK TO COVER WALLS EXCEPT BEHIND SERVICE, NORTHEAST WALL. A REINSPECTION FEE WILL BE ASSESTED NEXT INSPECTION IF NOT IN COMPLAINCE WITH PREVIOUS WRITE- UP AND N.E.C. |
|
| 11/09/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 11/09/00 SIZE NEUTRAL ACCORDINLY TO LOADS DERATE CURRENT CARRING CONDUCTORS IN 2" CONDUIT STRAP A/C CABLE AS PER CODE MAKE UP NOT FINISHED BOX BY DOOR SOUTHSIDE |
|
| 11/07/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* NEUTRALS AND GROUNDS MUST BE SEPERATED AT 12X2 J-BOX, N OT ALLOWED ON SAME GROUND BAR 250-24-1 PUSH-IN PLASTIC BUSHING NOT ALLOWED OR APPROVED IN PANCAKE BOXES FOR EXTERIOR LIGHTING 373-5 B WIRING METHODS IN PATIENT CARE AREAS (LIGHT SWITCHES) MUST COMPLY WITH 517-13 N.E.C. DE RATE CURRENT CARING CONDUTORS INSTALLED IN 2" CONDUIT. 310-15B N.E.C. INSTALL PERMANENT ADDRESS LABEL ON SERVICE |
|
| 11/06/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* BOND JUNCTION BOX 250-96 LOOSE FITTINGS NEED ACCESS TO ALL AREAS STRAP ALL CONDUITS AS PER CODE |