Permit: T00CM04703

Parcel: 12316003A


Addresses:

1214 E DRACHMAN ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
04/12/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
04/10/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/4 X 12 BEAM BY ENTRY REQUIRES 3-2 X 6 POST NORTH END, 4/6 BLOCKING MISSING IN GARAGE, PROVIDE TRUSS CHORD BLOCKING PER /5. OF PLAN NOT COMPLIED WITH ON SOUTH SIDE
04/03/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*
03/26/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. ALL EXTERIOR STUDS REQUIRE H2.5 CLIPS EVERY STUD AND HEADER TO STUDS SEE 1/6. 2. TRUSSES REQUIRE BLOCKING TOP AND BOTTOM EACH END. 3. 4 X 12 BEAM BY ENTRY REQUIRES 3-2 X 6 POST EACH END. 4. 4/6 BLOCKING MISSING. 5. HAVE ARCHITECT PROVIDE POST REQUIREMENTS FOR ALL BEAMS OR COMPLY WITH 3/6. 6. PROVIDE TRUSS CHORD BLOCKING PER /5. OF PLAN. 7. CLIP TRUSSES AT BEARING WALL PER 1/5 OF PLAN. 8. LSTA 9'S MISSING 1/5. 9. TRUSSES NOT BRACED PER TRUSS DRAWINGS. 10. TRUSS DRAWINGS MUST BE C.O.T. APPROVED.
03/22/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0950*/NOT COMPLETE ENOUGH TO INSPECT.