Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* ELECTRICIAL CONTRACTOR HAS COMPLIED TO LAST WRITE UP OK C/O F/O SUBJECT TO FINAL APPROVAL ALL INSPECTIONS |
|
| 01/16/2001 | ELECTRIC - FINAL | Partial Approval | OK TEMP C OF O FINAL APPROVAL SUBJECT LETTER FROM ELECTRICAL CONTRACTOR ASSUMING RESPONSIBILITY FOR THE INTERGITY OF THE ELECTRICAL WIRING NEW AND EXISTING TO BE IN A SAFE OPERATIONAL CONDITION |
|
| 01/12/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NOTES STRAP MC ABOVE CEILING WITHIN 12" EACH BOX AND AT 6' INTERVALS UP DATE PANEL SCHEDULES DE RATE CONDUCTORS IN NEW PANELS IN 1 1/4" CONDUITS(BOTH PANELS) INSTALL SIEZMIC WIRES ON ALL 2X4 LAY IN FIXTURE (2 EACH) AND 2# 8 SCREWS THRU GRID TO FIXTURE. 300-14 NEC, LEAVE TILES OPEN FOR INSPECTION |
|
| 01/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NOT READY FOR FINAL ABOVE CEILING INSPECTION NOT CALLED IN PRIOR TO FINAL INSPECTION VARIOUS MC CABLE, CONDUIT, ROMEX ETC,. NOT SUPPORTED PROPERLY, SUPORT PER N.E.C. AND REMOVE CEILING TILES BELOW ALL NEW ELECTRICAL INSTALLATIONS AND CALL FOR ABOVE CEILING INSPECTION TYPE UF ROMEX INSTALL OUTSIDE FRONT WAS COVERED PRIOR TO INSPECTIONS, UF INSTALLED THRU CONCRETE SLAB NOT APPROVED METHOD NEC 339-3 |