Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2000 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* MUST POST BOND FOR TEMP POWER OR HAVE OTHER TRADE FINALS PRIOR TO CLEARANCE FOR POWER |
|
| 12/12/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* INSTALL BONDING BUSHINGS OR LOCKNUTS ON BOTH ENDS OF ALL NIPPLES AND CONDUIT TERMINATION OF ALL SERVICE RELATED ENCLOSURE. 250-94 NEC. BOND GAS PIPING 250-104 NEC INSTALL PERMANENT ADDRESS LABEL ON METER BASE, AND LABEL DISCONNECT SWITCHES SHOWING DESIGNATION 230-70 NEC |