Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/08/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) UNITS NOT ENERGZIED, INSPECTOR WILL NOT TURN MAIN BREAKERS ON 2.) PUSH IN GROMMETS NOT APROVED UNLESS CLAMP TYPE, ITEM #5. |
| 02/20/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) SOME OUTLETS NOT ENERGIZED 2.) CONDUIT IN WATER HTR ROOM TO BE INSULATED WHERE TOUCHING COPPER WATER LINE. 3.) INSTALL BREAKER LOCK-OUT FOR WATER HTR. BREAKERS. 4.) PLEASE POWER CHECK ALL DEVICES PRIOR TO FINAL INSPECTION. 5.) INSTAL ROMEX CONNECTORS ON FUME HOOD IN KITCHEN. |
| 10/08/2001 |
ELECTRIC - FINAL |
|
Denied |
1.) #6 WIRE FOR SUB PANEL NOT ADAQUATE FOR 100 AMP CIRCUIT BREAKER SIZE PER N.E.C. 2.) SEAL ROOF PENETRATION PROPERLY WATER IS LEAKING THRU. RAIN. |