Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2001 | ELECTRIC - TEMPORARY POLE | Approved | IVRS - Inspection 0000*OK TO CLEAR TEMP PLE. OK CABLE DROP. | |
| 10/16/2001 | ELECTRIC - TEMPORARY POLE | Denied | 1.) DON NOT USE OSB BROAD TO SUPPORT SERVICE 2.) SECURELY MOUNT SERVICE TO PLYWOOD. 3.) DRIVE GROUND ROD BELOW SERVICE TO GRADE. 4.) ADD A SUPPORT TO RISER WITHIN 3" OF SERVICE 5.) BOTTOM HOLES POORLY SEALED. |