Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/27/2000 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*/APPROVED TO 2 FT SOUTH OF ADDITION. |
| 12/22/2000 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/1. SANITARY T FITTINGS NOT ALLOWED IN HORIZONTAL DRAIN. 2. SHORT RADIUS BENDS NOT ALLOWED FOR HORIZONTAL FLOW DIRECTION CHANGES. 3. REVERSE FLOW ON SOME DRAIN PIPES. 4. SEWER DRAIN PIPE MUST BE CONTINOUSLY SUPPORTED ON NATURAL/COMPACTED SOIL OR SELECT FILL. 5. WATER CLOSED NOT PROPERLY VENTED. 6. SHOWER NOT VENTED. 7. W/C NOT VENTED. 8. TUB NOT INSTALLED. YOU MUST BUILT TO PLAN OR REVISE PLAN TO AS BUILT YOU DO NOT HAVE TO BUT I RECOMMEND THAT YOU GET A LICENSED PLUMBER |