Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2000 | ELECTRIC - INTERMEDIATE | Approved | ||
| 10/16/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS, HOWEVER CHECK BOND (REDUNDENT) GROUND |
|
| 10/12/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* PROPERLY TERMINATE HOSPITAL GRADE MC CABLE PER MANUFACTURER INSTRUCTION (NOTE THE REDUNDENT GROUND "I BELIEVE" NEED TO BE FOLDED BACK AND PROPERLY TERMINATED BETWEEN MC CLAMP AND MC GEE MANUF. INSTRUCT) TO VERIFY INSTALL EQUIP GROUNDING CONDUCTOR TO ALL SWITCHES AND J-BOXES (IN EMT INSTALLATION) IN PATIENT CARE AREAS PER ART 517 |