Permit: T00CM04626

Parcel: 11520198A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM04626

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
08/20/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TO CLEAR NEED TO SEE CONNECTIONS TO DBS AFTER CROSSOVER.
07/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) NEED LETTER TO VERIFY TORQUE VALVES DURING INSTALLATION OF EQUIPMENT. 2.) LABEL DISCONNECT SWITCHES AND BREAKERS. 3.) NEED REVISED PLAN TO REFLECT EQUIPMENT 4.) PLEASE HAVE LOCKABLE COVERS INSTALLED FOR RECPTICALS.