Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM04623

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2000 FRAMING Approved IVRS - Inspection 0000*
11/15/2000 FRAMING Denied IVRS - Inspection 0999*/1. HANGER ON 4 X 8 BEAM MUST BE REPLACED SEE ITEM #1 FROM 11-14-00 2. MBR TUB AND SHOWER AND FIXTURES NOT IN.
11/14/2000 FRAMING Denied 1. HANGER ON 4 X 8 BEAM BY ENTRY/GARAGE FRONT DAMAGED AND NOT INSTALLED PROPERLY INSTALL 6X HANGER. 2. DUCT RESTRICTED BY GARAGE SUPPLY PLENUM TOO TIGHT OF BEND 3. NO TEST ON PEX. 4. SUPPORT 4 SW ELECTRIC BOX 2 ENDS. 5. ELECTRIC NOT ALLOWED IN RETURN AIR PLENUM 2ND FLOOR. 6. 1/2" CLEARANCE TO COMBUSTALBES REQUIRED AT KITCHEN RECESSED LIGHT 7. WIRE CUT KITCHEN AND NOT SECURE. 8. MBR TUB AND SHOWER NOT IN 9. W/H VENT BLOCKED BY COPPER PLUMB. 10. STAIRWAY SMOKE DETECTOR MISSING STOPPED INSPECTION TOO MANY ITEMS.