Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T00CM04622
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2000 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000*/1. PROVIDE GAS TEST MIN. 10 PSI. 2. PROVIDE MIN. 1" CLEARANCE FROM COMBUSTIBLES AT ALL FLUES. 3. STRAP OVER BORED WATER AND GAS AT DBL. TOP PLATE. 4. ATTIC ACCESS BLOCKED WITH MECHANICAL. 5. DRYER DUCT NOT THROUGH ROOF. 6. SUPPORT 90 DEGREE VTR, HALL LAUNDRY. 7. EXHAUST FAN AT MASTER BATH INSTALLED UPSIDE DOWN. 8. CONDENSATION NOT COMPLETE AT FURNACE. | |
10/23/2000 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/1. BLOCK STUB TRUSSES (A3) AT BOTTOM, WILL CHECK AT INTERMEDIATES. 2. PROVIDE DETAIL 13/DO1, WILL CHECK AT INTERMEDIATES. |