Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/02/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/26/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ MEZZANINE - 12" FLEX DUCT RUN - RE-ROUTE DUCT BELOW STEEL PERLING. SQUARE/ROUND FLEX DUCT TRANSITIONS, INSULATE BOXES WITH FOIL BACK INSUL. RE-ROUTE 14" FLEX DUCT PROVIDE ACCESS TO AREA. ROOFTOP - 1) 2 TON, 24,000 BTUH, UNIT INCORRECT FUSE SIZE. 2) RE-ROUTE COND DRAIN. 3) COMPLETE ELEC. DATA PLATE AUX. HT STRIP, YES? NO? |