Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/13/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 10/12/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/1. JOIST HANGERS AT BACK PORCH NOT SIZED CORRECTLY AND NOT ALL NAILED. 2. STEEL LET IN BRACES REQ' 2 NAILS EACH END. 3. OPEN INSPECTION HOLE AT FRONT COLUMNS NEAR BOTTOM. 4. HGUS5412 HANGER UPSTAIRS FRONT NOT NAILED. 5. PROVIDE CONVERSION CHART FOR TIMBER-STRAND HEADER SIZES. 6. RE-CHECK ROOF NAILING (LOTS OF SHINERS). |