Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T00CM04554
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2000 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
12/12/2000 | BUILDING - FINAL | Denied | 1. TYPE B FLUE PIPE AND CAP, BOTTOM OF CAP NEEDS TO BE 12" ABOVE ROOF PENETRATION UBC 806.6. 2. FIRE TAPE/CAULK PENETRATION FROM REFRIGERANT LINE TO ATTIC. 3. PROVIDE 6" CLEARANCE FROM SINGLE WALL FLUE PIPE TO COMBUSTIBLE MATERIALS. 4. PROVIDE POSITIVE SUPPORT FOR AC CONDENSOR USE SAME AMP FUSES REQUIRED BY MANF. 5. CUT NAILS AT SLAB HAZARDOUS CONDITION. |