Permit: T00CM04544

Parcel: 110151180


Addresses:

2420 N CRAYCROFT RD

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/15/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0920*
DOOR LOCKED NO ACCESS INSIDE
REGARDLESS OF WHO IS RESPONSIBLE FOR THE UNIT HEATER, IT STILL NEEDS TO BE ADDRESSED BEFORE FINAL INSPECTION
12/12/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
UNIT HEATER IN THE BACK ROOM IS NOT VENTED PROPERLY. THE VENT OUTLET ON THE HEATER IS 5" YOU CANNOT REDUCE TO 4" RUN SAME SIZE VENT ALL THE WAY THROUGH THE ROOF. CORRECT AND FOR FINAL