Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T00CM04532
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2001 | MECHANICAL - HOODS | Approved | IVRS - Inspection 0000* | |
04/24/2001 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000* | |
04/23/2001 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000* 1) HOW WAS 3" CLEARANCE ON LEFT SIDE OF RATED CHASE ACHIEVED? ONLY 1 LAYER OF 5/8" ROCK EXPOSED. THERE SHOULD BE 2 2) EXSISTING A/C COMB. UNIT ON ROOF CORRECT AS NECESSARY 3) EXPOSED CONTROL WIRING LAYING ON ROOFDETERIATED FROM WEATHER 4) CONDENSATE DRAINS LINE LAYING AND TERMINATING ON ROOF SURFACE |
|
04/13/2001 | MECHANICAL - HOODS | Denied | IVRS - Inspection 0999*REMOVE EXHAUST FAN & OPEN SHAFT FOR INSPECTION ON GREASE DUCT CLEARANCE. MUST HAVE MIN. 3" CLEARANCE ON ALL SIDES. OK TO COVER CEILING. | |
03/01/2001 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000* 1 HR RATED SHAFT |