Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/01/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/30/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/NO CHANGE FROM 11-29-00. |
| 11/29/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. PROVIDE ENGINEERING APPROVED AND C.O.T. APPROVED POST TENSION SLAB REPAIR. 2. PROTECT ABS IN FLOOR REPAIR KITCHEN. 3. HANGER FOR 2 X 6 ABOVE ATTIC ACCESS BENT/DAMAGED AND DOES NOT SUPPORT TRUSS REPLACE. 4. MBR DUCT KINKED. 5. ELECT OUTLET GFCI REQ 24" OF RT SIDE OF K. SINK. 6. SHEAR WALL 4 REQUIRES 17/SD3 NOT COMPLIED WITH BLOCK BETWEEN LADDER BACK. 7. SHEAR WALL 2 REQUIRES SEE 18/SD3. |