Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/15/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* CORRECT WIRING IN 12 POLE L-1 PNL INSTALL CLASS R FUSES PROVIDE CLEARANCE IN FRONT POWER CABINET 200 A MAIN SERVICE DISCONNECT SCRAPE PAINT BEHIND GROUND |