Permit: T00CM04488

Parcel: 114462090

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM04488

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
RE ROUTED 2" CONDUIT
11/29/2000 ELECTRIC - FINAL Denied GROUND RODS STILL NOT EXPOSED AS REQUIRED ON PREVIOUS INSPECTION
2" CONDUIT AND SEALTITE VIOLATIONS WORKING CLEARANCE IN FRONT OF CABINATES. NEC 110-26 RE ROUTE ANTENNA CABLES TO ALLOW HEADROOM ASLO NOTE THAT FINAL INSPECTION WAS CALLED PRIOR TO UNDERGROUND AND UFER INSPECTIONS A RE FEE WILL BE ASSESTED IF NOT IN COMPLIANCE FOR NEXT INSPECTION
11/27/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
EXPOSE ALL GROUND RODS
COMPLETE WIRING OF SERVICE AND ASSOCIATED EQUIPMENT