Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1)WASTE AND VENT SYSTEM AND WATER TEST TO TOP OF VENTS OK.2)GAS PRESSURE TEST OK.3)OVERLEAD WATER DISTRIBUTION OK.4)OK FOR DRYWALL UPON BUILDING INSPECTORS APPROVAL.5)ALL CORRECTIONS HAVE BEEN MADE.6)REVISED AND APPROVED DRAWING FOR GAS SYSTEM OK. | |
| 04/13/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) GAS SYSTEM WAS INSTALLED NOT TO PLAN 2) SEE SEC. 804.1 94 UPC FOR WASHING MACHINE TRAP AND STAND PIPE PROVISIONS 3) WOOD AND P TAPE ARE NOT APPROVED MATERIAL FOR STRAPING OF GAS LINE 4) MUST PROVIDE WATER TEST ON WASTE AND VENT SYSTEM ALL THE WAY TO THE TOP OF VENTS THRU ROOF |