Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* JOHN OCHOA INSURED THESE TWO ITEMS WILL BE TAKEN CARE OF: 1) 2" ABS DRAIN FOR DISHWASHER NEEDS APPROVED STRAP ( 2" ABS PIPE PROPPING UP DRAIN NOT APPROVED) 2) INSTALL CLEAN OUT COVER AT WATER HEATER LOCATION |
|
| 05/07/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) DRAIN ICE MAKER AND STORAGE BIN SEPERATLY TRAP AT FIXTURE OUTLET 2) SODA DISPENSER DRAIN NOT APPROVED 3) NEED TO SEE REVISED EQUIPMENT PLAN NOT INSTALLED PER PLAN |
|
| 05/04/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) ALL DOORS LOCKED NO ACCESS 2) UNABLE TO DO INSP. RETURNED FOR RE INSP.: 1) FLUSH HANDLE ON WRONG SIDE FOR ADAWC 2) ICE MACHINE AND STORAGE BIN DRAINS NOT APPROVED 803.0 94 UPC 3) THE TRAP SHALL BE THE SAME SIZE AS TRAP ARM 1003.3 94 UPC 4) KITCHEN APPLIANCES NOPT INSTALLED PER PLAN SEE 1013.094 UPC 5) SEE SEC 707.10 CLEARANCE FOR CLEAN OUTS |
|
| 04/25/2001 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection 0000* NEED TO SEE FINAL CONNECTIONS. GAS KIT. APPLIANECES AND PRESSURE TEST OK |