Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* NOTE - DON'T FORGET TO PROVIDE REVISED GAS 100 METRIC ON FINAL | |
| 03/15/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) NEED APPROVED GAS ISOMETRIC AND SIZING BEFORE FINAL INSP. 2) ABS DWV OK WATER TEST WAVIED THIS TIME ONLY 3) COPPER OK PRESSURE TEST OK 4) OK TO COVER WALLS |
|
| 03/13/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) WATER TEST ABS TO 42" 2) UNCOVER (SHEET ROCK, INSULATION) ALL PIPING 3) CHANGE FROM HAND SINK TO FLOOR SINK OK - CHANGE N/H BAND TO MISSION 4) NEED GAS ISOMETRIC APPROVED FOR CHANGE IN PIPING 5) COPPER PIPING OK PRESSURE TEST OK 6) GREASE TRAP APPROVED BY VVC REDUCTION FROM 4" TO 2" AT TRAP WASTE CONSIDERED AN OBSTRUCTION. |
|
| 03/08/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) A REDUCTION IN THE WASTE LINE FROM 4" TO 2" IS CONSIDERED AN OBSTRUCTION OF FLOW AND NOT APPROVED. 2) A GREASE TRAP OF MORE THAN 55QPM IS ALLOWED ONLY WHEN FIRST APPROVED BY THE ADMINISTRATIVE AUTHORITY | |
| 03/07/2001 | PLUMBING - INTERMEDIATE | Denied | OK TO COVER WALLS GREASE TRAP NOT APPROVED | |
| 03/02/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) I MUST SEE ALL CONNECTIONS AND PIPE IN RELATION TO THE GREASE TRAP 2) OUTLET OF GREASE TRAP CONSIDERED AN OBSTRUCTION 3) I NEED TO SEE ALL GAS PIPING AND CONNECTIONS IN RELATION TO GAS INSTALLATION |