Permit: T00CM04456

Parcel: 122170930


Addresses:

1250 N HOWARD BL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
03/21/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
03/19/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/1. SEWER LINE MUST BE A MINIMUM OF 12" BELOW GRADE TO TOP OF PIPE AT EXIT OF BUILDING PER UPC SECTION 718.3 PRESENTLY ABOVE GRADE. YOUR PLAN IN SECTION A/4 SPECIFIES 2'-6" TO GRADE FROM FINISHED FLOOR. AND SEWER IS ONLY 2'4" TO PLAN AND CODE. IF YOU DESIRE TO BACKFILL YOUR LOT TO 12" ABOVE SEWER THEN YOU MUST REUSE YOUR PLAN AND HAVE IT APPROVED BY CITY OF TUCSON. NEXT FAILING WILL BE CHARGED A REINSPECTION FEE.
03/16/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/1. SEWER LINE MUST BE A MINIMUM OF 12" BELOW GRADE TO TOP OF PIPE AT EXIT OF BUILDING U.P.C. SECTION 718.3. PRESENTLY ABOVE GRADE.