Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/23/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/09/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/NO CHANGE SITE CONFERENCE. |
| 02/07/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. PAHD42 HOLD DOWN REQUIRE A MINIMUM OF 12 EACH 16D NAILS ONLY 6-8 NAILS INSTALLED-HOLD DOWNS COVERED W/O INSPECTION EXPOSE. 2. DRYWALL SCREWS NOT ALLOWED FOR INSTALLATION OF SIMPSON HARDWARE. 3. LTT19 PERLIN ANCHORS NOT INSTALLED. 4. HTT22 HOLD DOWNS MUST BE ATTACHED TO FULL LENGTH DOUBLE STUDS NOT TO TRIMMERS. 5. PROVIDE TJI INSTALLATION INSTRUCTIONS FOR RAFTER TAILS AND LOOK OUTS. |