Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T00CM04402
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/05/2001 | ELECTRIC - INTERMEDIATE | Approved | ||
02/15/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | OK UNDER FLOOR WIRING METHODS. 1) LOOSE LOCKNUTS AT PANELS-NIPPLES 2) NEED PROTECTION FOR CONDUCTORS AT NIPPLE 3) IDENTIFY NEUTRAL CONDUCTOR 4) IDENTIFY ALL PHASE CONDUCTORS | |
02/13/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) SUPPORT CONDUIT AS PER CODE 2) OPEN AREAS IN FLOOR AS MARKED TO VIEW M/C CABLE OK WALLS ROOM #107-112, 115 EXCEPT ONE SIDE PANEL WALL |
|
01/30/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* NOTE PLANS STATE NOT TO USE M/C CABLE, NEED LETTER FROM ARCHITECT OR ENGINEER AUTHORIZING USE |