Permit: T00CM04391
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1) GAS PRESSURE TEST OK 2) WASTE AND VENT SYSTEM OK 3) SOIL WATER TEST OK 4) OK FOR DRYWALL UPON BLDG INSP. APPROVAL |
|
| 05/14/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) PARTIAL ON GAS REGULATOR WILL BE INSTALLED AT A LATER DATE 2) 1 WASTE AND VENTS PLAN CALLS FOR 2" VENT AT BAR OR MOP SINK 1 1/2" HAS BEEN INSTALLED 3) PROVIDE PROPER ACCESS PANEL FOR TRAP PRIMER AND WATER HAMMER A PLUMBER SEE NOTE #25 |
|
| 04/27/2001 | PLUMBING - INTERMEDIATE | Not ready for Inspection | NOT READY ON TOP OUT TEST ON NEW 4" SITE SEWER TO EXSISTING OK TO BACKFILL |