Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T00CM04357
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2000 | ELECTRIC - SERVICE UPGRADE | Approved | 10/17/00 OK TO CLEAR | |
10/16/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* DID NOT COMPLY WITH PREVIOUS INSPECTION WRITE UP (METER BOX) MAIN GROUNDING LUG IS LOOSE DUE TO USE OF SELF TAPPING SCREW, NOT ALLOWED MUST BE THREADED TAP OR NUT AND BOLT NEC 90-4 |
|
10/12/2000 | ELECTRIC - SERVICE UPGRADE | Denied | BUFF OFF ENAMEL PAINT BEHIND GROUND LUGS TO INSURE GROUND CONTINUITY TO ENCLOSURES. INSTALL BOND BUSHING ON OFFSET NIPPLE FOR RECEPTACLE |
|
10/10/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* BONDING BUSHING OR BONDING LOCKNUTS REQUIRED 250-94 NEC CHASE NIPPLES NOT ALLOWED PERMANENT ADDDRESS LABEL |