Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/01/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/31/2000 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/1. DRAFT STOP MINIMUM 1 INCH THICK ABOVE ENTERTAINMENT AREA SEPERATING UNBLOCKED CAVITY TO ATTIC. |
| 10/26/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. BLOCK #2 SHEARWALL 2. SECURE PERIMETER AT #3 SHEARWALL AT GARAGE AT FLOOR. 3. FHA STRAP 16 GA REQUIRED AT OVER BORED DBL TOP PLATE EXTERIOR ABOVE PANEL. 4. PROTECT ELECTRICAL WITHIN 1 1/4" FROM EDGE OF STUD. 5. PROVIDE NAILS AT OVER KNOTCH 16GA STRAP FOR REFRIGERANT LINE. 6. COMPLETE ELECTRICAL AT EXHAUST FANS. 7. BLOCK MECHANICAL 3 SIDES MINIMUM. 8. PROVIDE WEDGE ANCHOR BACK SLIDER WITHIN 12"S OF SOLE PLATE SPLICE. |