Permit: T00CM04300

Parcel: 107143480

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
09/24/2001 ELECTRIC - CABLE DROP Approved
09/18/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*1.) SEE ATTACHED SHEET FOR TEMP POWER REQUIREMENTS 2.) STRAP RISER WITH MININIUM 2 STRAPS BELOW ROOF LINE 1/4" HARDWARE MININIUM 3.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED CONDUCTOR OR PROVIDE MAIN BONDING JUMPER 250-24. 4.) USE 1/4" MININUM HARDWARE TO SECURE PANEL TO STRUCTURE 5.) PROVIDE LISTING FOR MULTIPOLE. CONDUCTORS UNDER LUG AT GROUND BAR. 6.) STRAP GROUNDING ELECTRODE CONDUCTORS TO STRUCTURE.