Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/07/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/06/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*NOTES 935 RE-INSPECTION FEE IS ASSESED. 1.) UNIT #6 OUTSIDE GFCI OUTLET NOT WORKING PROPERLY 2.) SOME CIRCUITS NOT ENERGIZED, INSPECTOR WILL NOT TURN ON CIRCUIT BREAKERS 3.) AS PER LAS INSPECTION WRITE UP HAVE ELECTRICAL CONTRACTOR POWER CHECK ALL UNITS. PAY RE FEE 201 N STONE PRIOR TO FUTURE INSPECTIONS. |
| 09/05/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) I.D. BREAKER IN SUB PANEL. 2.) UNLOCK UTILITY ROOMS. 3.) HAVE ELCTRICAL CONTR, POWER CHECK ALL UNITS, LEAVE POWER ON TO INSPECT. RE-CALL FOR FINAL WHEN READY. |
| 08/21/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 08/20/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) ROOF EQUIPMENT NOT CONNECTED MECH TIE INS 2.) MARK PANEL SCHEDULES 3.) TAPE WHITE CONDUCTORS BLK OR RED AT WATER HEATERS 4.) INSTALL ALL DEVICE COVERS 5.) FINISH INSTALLING FANS IN BEDROOMS. |