Permit: T00CM04291

Parcel: 131091910


Addresses:

5619 E 28TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
01/18/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
01/11/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0220*NOT APPROVED CORRECT PER NOTES BELOW. 1.) WHEN GRADE IS LEVEL THE GROUND RODS WILL HAVE TO BE DRIVEN TO A LEVEL OF 2" BELOW GRADE. 2.) THE EXPOSED GROUNDING WIRE WILL NEED SEVERAL CLAMPS. CLAMP TO BLOCK WALL. DO NOT DEPEND ON THE RISER CONDUIT TO SUPPORT THIS WIRE. 3.) THE WATER PIPING AND GAS PIPING MUST BE GROUNDED TO THE GROUND BAR IN THE CIRCUIT BREAKER SECTION.