Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/27/2000 FRAMING Approved IVRS - Inspection 0000*
10/26/2000 FRAMING Denied IVRS - Inspection 0999*/1. SHEARWALL #2 FRONT PROVIDE SHEAR TRANSFER FROM SOLE PLATE THRU ROOF DIAPHRAM. 2. PROTECT PEX, ELEC WITHIN 1 1/4" FROM EDGE OF STUD. 3. LADDER BLOCKS NOT NAILED TO DBL TOP PLATE. 4. COMPLETE DRAFT STOP. 5. GROUT TUBS 6. FIX LEAK AT MASTER BATH TUB. 7. SECURE ABS 4' O.C. HORIZONTALLY. 8. PROVIDE DBL STUDS UNDER GIRDER AT FRONT CLIP BOTH SIDES.
10/25/2000 FRAMING Partial Approval PENDING ROOF DRY IN AND EXTERIOR DRY IN.