Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/13/2000 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/12/2000 |
BUILDING - FINAL |
|
Denied |
1. AC DISCONNECT FUSES NOT AS PER MANF. SPEC'S. 2. EXHAUST FAN NOT OPERABLE AT HALL BATH. 3. NO LADDER PROVIDED FOR ATTIC INSPECTION. 4. PROVIDE BOND BUSHING AT ELEC. PANEL CONCENTRIC KNOCK OUTS FOR IRRIGATION INSTALLED AND PROVIDE KNOCK OUT PLUG AT IRRIGATION BOX. |
| 12/11/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. PROVIDE ALL NECESSARY PAPERWORK. 2. MASTER BATH COUNTER TOP AND SINK NOT COMPLETE. 3. EXHAUST FAN AT HALL BATH HAS NO POWER. 4. NO ACCESS TO ATTIC. 5. PROVIDE CORRECT FUSES AT AC DISCONNECT. |