Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T00CM04273
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2000 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
12/12/2000 | BUILDING - FINAL | Denied | 1. AC DISCONNECT FUSES NOT AS PER MANF. SPEC'S. 2. EXHAUST FAN NOT OPERABLE AT HALL BATH. 3. NO LADDER PROVIDED FOR ATTIC INSPECTION. 4. PROVIDE BOND BUSHING AT ELEC. PANEL CONCENTRIC KNOCK OUTS FOR IRRIGATION INSTALLED AND PROVIDE KNOCK OUT PLUG AT IRRIGATION BOX. | |
12/11/2000 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/1. PROVIDE ALL NECESSARY PAPERWORK. 2. MASTER BATH COUNTER TOP AND SINK NOT COMPLETE. 3. EXHAUST FAN AT HALL BATH HAS NO POWER. 4. NO ACCESS TO ATTIC. 5. PROVIDE CORRECT FUSES AT AC DISCONNECT. |