Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/14/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/13/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) DUCT RESTRICTED 2) FURNACE VENT NOT IN 3) GAS LINE NOT COMPLETE 4) SUPPORT 3/4 GAS LINE AT 8' ON CENTER 5) 3RD STEP FROM TOP REVERSE PITCH 6) BLOCK DUCT BOOT 3 SIDES |
| 11/07/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE BANG PLATES AT PLUMBING 2) SECURE PLUMBING AT CEILING 3) PROVIDE FIRE BLOCKING AT LOWER LEVEL BATHROOM AND 2ND FLOOR |
| 09/26/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |