Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/24/2000 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/22/2000 |
BUILDING - FINAL |
|
Denied |
1. ITEMS FROM PREVIOUS INPECTION NOT COMPLETE. 2. LOW VOLTAGE IN HIGH VOLT BOX. 3. SELF CLOSING DOOR AT GARAGE DOESN'T SELF CLOSE. 4. COMPLY WITH SEC 210 8 (A) (4) NEC SERVICE OUTLET ON SAME LEVEL WITHIN 25'. 5. RE INSPECTION FEE REQUIRED. |
| 11/20/2000 |
BUILDING - FINAL |
|
Denied |
1. EXTERIOR FIXTURE/COVER NOT INSTALLED. 2. IN ATTIC LOW VOLTAGE/HIGH VOLTAGE IN SAME OUTLET BOX RELOCATE. 3. PROVIDE A SERVICE OUTLET FOR AND LIGHTING FIXTURE CONTROLLED BY A SWITCH SEE NOTE #2 UNDER ELECTRICAL LEGEND. 4. OUTLETS UNDER ISLAND PENINSULAR COUTER TOP EXCEEDING 6"S NOT ALLOWED SEE NEC 99 ARITCLE 210-52 SEE C #5. 5. IDENTIFY SMOKE DETECTORS AT PANEL AS PER SHEET 9A. |