Permit: T00CM04234

Parcel: 117022820


Addresses:

515 E 2ND ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T00CM04234

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
05/31/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) ELECTRIC OUTLET GFCI HOT WHEN TRIPPED 2) BARE BULB LIGHT FIXTURES NOT ALLOWED IN CLOTHES CLOSETS 3) WATER HEATER VENT INPROPERLY INSTALLED VENT CONNECTOR MUST CONNECT INSIDE OF INNER LINER OF "B" VENT, 6" CLEARANCE REQUIRED TO COMBUSTIBLES ON SINGLE WALL VENT 4) LABEL ALL CIRCUITS IN ELECTRIC SERVICE PANEL 5) FIREPLACE GAS LOG GAS LINE MUST HAVE FIRE PROOF CAULK AT FIRE PLACE PENETRATION 6) PROVIDE STUCCO AND INSULATION INSTALLATION CERTIFICATES NOTE: IS DISPOSAL AND DISH WASHER ON A MULTI WIRE CIRCUIT