Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/23/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 04/19/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/1) KITCHEN COUNTERS WIDER THAN 12" MUST HAVE GFCI OUTLET 2) NO PRESSURE TEST ON GAS LINES 3) WATER HEATER "B" VENT NOT INSTALLED MUST HAVE 1" CLEARANCE TO COMBUSTABLES |
| 04/18/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0925*/NO ACCESS OR PLAN |
| 04/17/2001 |
FRAMING |
|
Cancelled |
IVRS - Ri canceled |
| 04/02/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. WINDOWS ARE NOT PER PLAN. REVISE PLAN TO AS BUILT. 2. NAIL PROTECT WIRES AT N.W. CORNER TOP PLATE-WITHIN 1 1/4" OF STUD SURFACE. 3. GAS LINE REQUIRES ON ELECTRIC BOND. 4. EXISTING HOUSE HAS BEEN COMPLETELY REWIRE-HAD WATER CLOSET DRAIN LINE REPLACED, ADDED GAS LINE TO RANGE AND HAD ALL MECHANICAL DUCTS REPLACED WITHOUT INSPECTION. REVISE PLAN TO AS BUILT. |
| 02/28/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/FRAME OK WILL APPROVE AFTER PLUMB AND ELECTRIC. |