Permit: T00CM04234

Parcel: 117022820


Addresses:

515 E 2ND ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM04234

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2001 FRAMING Approved IVRS - Inspection 0000*
04/19/2001 FRAMING Partial Approval IVRS - Inspection 0000*/1) KITCHEN COUNTERS WIDER THAN 12" MUST HAVE GFCI OUTLET 2) NO PRESSURE TEST ON GAS LINES 3) WATER HEATER "B" VENT NOT INSTALLED MUST HAVE 1" CLEARANCE TO COMBUSTABLES
04/18/2001 FRAMING Denied IVRS - Inspection 0925*/NO ACCESS OR PLAN
04/17/2001 FRAMING Cancelled IVRS - Ri canceled
04/02/2001 FRAMING Denied IVRS - Inspection 0999*/1. WINDOWS ARE NOT PER PLAN. REVISE PLAN TO AS BUILT. 2. NAIL PROTECT WIRES AT N.W. CORNER TOP PLATE-WITHIN 1 1/4" OF STUD SURFACE. 3. GAS LINE REQUIRES ON ELECTRIC BOND. 4. EXISTING HOUSE HAS BEEN COMPLETELY REWIRE-HAD WATER CLOSET DRAIN LINE REPLACED, ADDED GAS LINE TO RANGE AND HAD ALL MECHANICAL DUCTS REPLACED WITHOUT INSPECTION. REVISE PLAN TO AS BUILT.
02/28/2001 FRAMING Partial Approval IVRS - Inspection 0000*/FRAME OK WILL APPROVE AFTER PLUMB AND ELECTRIC.